07 UK HYDRONICS GEN 24 LR - Flipbook - Page 23
R290
INDEX HYDRONICS AND ROOFTOPS
CHILLERS AND HEAT PUMPS
Technical performance
Size
Voltage
Power supply
V
Phase
Frequency
Hz
ECOi-W AQUA-G BLUE 50-80 H EC fan - heat pump
50
60
70
80
400
400
400
400
Three phase
Three phase
Three phase
Three phase
50
50
50
50
P-AQAG0050HA
P-AQAG0060HA
P-AQAG0070HA
P-AQAG0080HA
Cooling capacity 1)
kW
48,2
56,1
64,9
74,1
Input power 1)
kW
15,0
19,0
21,6
25,0
EER 1)
3,20
3,00
3,00
3,00
SEER 2)
ηs,c 2)
4,37
4,30
4,31
4,21
%
171,9
168,9
169,4
165,4
Heating capacity 3)
kW
49,2
61,1
73,5
83,6
Input power 3)
kW
15,6
18,6
21,7
24,9
COP 3)
3,2
3,3
3,4
3,4
SCOP 4)
ηs,h 4)
3,67
3,75
3,87
3,84
143,7
146,8
151,8
150,5
A+
A+
A++
A++
3,11
3,14
3,26
3,22
121,4
122,7
127,3
126,0
A+
A+
A++
A++
Energy efficiency class (SCOP) 4)
A+++ to D
SCOPMT 4)
ηs,hMT 4)
Energy efficiency class (SCOPMT) 4)
A+++ to D
Sound power (STD / S)
dB(A)
82,7 / 79,9
84,1 / 80,5
85,1 / 81,5
85,8 / 81,9
Sound pressure at 10 m (STD / S) 5)
dB(A)
56,1 / 51,9
54,7 / 52,5
57,1 / 53,5
57,8 / 53,9
Physical features
ECOi-W AQUA-G BLUE 50-80 H EC fan - heat pump
Height
50
60
70
80
1 730
2 011
2 030
2 030
2 215 / 2 215 6)
2 180 / 2 680
2 180 / 2 680
2 180 / 2 680
1 032
1 160
1 160
1 160
kg
538
603
628
669
1
1
1
1
kg
4,50
4,80
5,30
6,80
3 (100 years)
3 (100 years)
3 (100 years)
3 (100 years)
2 / Scroll
2 / Scroll
2 / Scroll
2 / Scroll
50 / 100
40 / 60 / 100
40 / 60 / 100
50 / 100
mm
Length w/o / w water tank
Dimension
Width
Operating weight
Refrigerant and compressors
Number of refrigerant circuits
Refrigerant (R290)
GWP
CO₂ eq.
Compressors
Number / type
Capacity steps
%
Water connections
Type of water connections
Water inlet/outlet diameter
Male gas threaded
Male gas threaded
Male gas threaded
Male gas threaded
Inch
1¼
2
2
2½
l
200
300
300
300
Buffer tank (option)
Volume
1) According EN14511-2013: chilled water inlet/outlet temperature: 12/7 °C, outdoor ambient temperature 35 °C DB. 2) According EN14825 and following COMMISSION REGULATION (EU) 2016/2281.
3) According EN14511-2013: warm water inlet/outlet temperature: 40/45 °C, outdoor ambient temperature 7 °C DB/6 °C WB. 4) According to EN14825 and following COMMISSION REGULATION (EU) No
813/2013. 5) Sound pressures refer to ISO 3744 standard, parallelepiped shape. 6) Tank is external to the unit chassis. Its width must be added.
* w/o: without, w: with.
Accessories and options
Accessories and options
Anti‑vibration rubber mount / spring dampers
Electrical heater for the water tank
Cascade controller
Variable or fixed speed pumps
Refrigerant gauges HP/LP
Water tank 200 l (size 50)
Shut off valves
Water tank 300 l (sizes 60‑70‑80)
Sofstarter
3 Way valve and probe for Domestic Hot Water management
Energy meter for input power
R290
HIGH
SEER
HIGH
SCOP
4,33
3,54
AIR
COOLED
PLATE HEAT
EXCHANGER
SCROLL
COMPRESSOR
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.