R410A
GENERAL INDEX
ECOi-W AQUA EVO H · R410A
Air cooled heat pumps Inverter.
Cooling capacity: 20,0 to 35,9 kW.
Heating capacity: 20,4 to 34,0 kW.
The range at a glance
· 1 version: H (heat pump)
· 2 sizes
Advantages
· Wide load variation capability:
‑ Cooling operation down to 30% and up to 140% of
nominal capacity
‑ Heating operation down to 40% and up to 130% of
nominal capacity
· Unit optimization in heating mode for both fan coil and
floor applications
· Wide operating limits in heating mode
· Domestic Hot Water management
· Inverter compressor
· New fan motors (ErP compliant) with integrated grill and
fan speed control as standard
Operating limits
To be confirmed with AC SELECT:
https://acselect.panasonic.eu/
Ambient temperature.
-10 °C
45 °C
-15 °C
-20
-15
30 °C
-10
-5
0
5
10
15
20
25
30
35
40
45
50
55
Leaving water temperature.
-8 °C 1)
18 °C
25 °C
-20
-15
-10
-5
0
5
10
15
20
25
30
55 °C 2)
35
40
45
50
55
Cooling: outside air temperature (°C (DB)). Heating: outside air temperature (°C (WB)).
1) Below 5 °C, glycol is required. For operation below 0 °C contact sales office.
2) Maximum leaving water temperature 55 °C (minimum outdoor air temperature -10 °C size 20,
-15 °C size 30) to be confirmed with AC SELECT.
Chillers suitable for operation without buffer tank for water content greater than 2,5 liters of water
per kW of output.
AC SELECT.
Smart and user-friendly the new air conditioning
selection program: https://acselect.panasonic.eu/
20
Equipment
· Inverter driven compressor
· Plate evaporator (AISI 316)
· A single inverter driven 3‑phase scroll compressor
equipped with variable frequency brushless motor (20‑
120 Hz)
· 1 refrigerant circuit
· Bi‑flow electronic expansion valve
· Multistage centrifugal pump as standard
· Bluefin coil
· Operating low water content in the plant
· Automatic circuit breaker
· Coil grilles
· Fan speed control
· Power factor corrector capacitors
· Phase sequence control
· Soft starter
· Water differential pressure switch
· Water filter
· DHW function available on the controller with DHW probe
and 3 way valve available as options