07 UK HYDRONICS GEN 24 LR - Flipbook - Page 113
R32
INDEX HYDRONICS AND ROOFTOPS
ROOFTOPS
Technical features
Size
ECOi-RT-Z H - heat pump
105
120
140
P-RTZ0105HA
P-RTZ0120HA
P-RTZ0140HA
Cooling capacity 1)
kW
106
119
139
Input power 1)
kW
31,5
36,8
43,0
3,37
3,23
3,24
106
119
139
3,82
3,82
3,67
EER 1)
Pdesign 2) 3)
kW
SEER 2) 3)
Energy efficiency class 2) 3)
ηs,c 2) 3)
A+ to E
B
B
B
150
150
144
Heating capacity 1)
kW
106
117
142
Input power 1)
kW
27,0
30,3
38,0
3,72
3,89
3,69
100
118
140
3,36
3,56
3,32
COP 1)
Pdesign 2) 3)
kW
SCOP 2) 3)
Energy efficiency class 2) 3)
ηs,h 2) 3)
A+ to E
B
B
B
131
130
130
Electrical data
Voltage
Power supply
V
Phase
Frequency
Maximum operating intensity
400
400
400
Three phase
Three phase
Three phase
Hz
50
50
50
A
79,0
85,0
105,0
Refrigerant and compressors
Number of refrigerant circuits
Compressors
Number / type
Mounting type
Capacity steps
2
2
2
2 / Scroll
2 / Scroll
2 / Scroll
Single
Single
Single
0 / 50 / 100
0 / 50 / 100
0 / 50 / 100
Copper tubes and aluminium fins
Copper tubes and aluminium fins
Copper tubes and aluminium fins
%
Indoor coil
Coil type
Number of rows
Front surface
4
4
4
3,24
3,24
3,24
Copper tubes and aluminium fins
Copper tubes and aluminium fins
Copper tubes and aluminium fins
3
3
3
1,50
1,50
1,50
Backward curved centrifugal
Backward curved centrifugal
Backward curved centrifugal
m²
Outdoor coil
Coil type
Number of rows
Front surface
m²
Indoor fans - EC type
Fan type
Number of fans
Air flow rate
Min. / Nominal / Max.
Motor power
m³/h
kW
2
2
2
15 360 / 19 200 / 23 040
17 200 / 21 500 / 25 800
20 400 / 25 500 / 30 600
4,23
4,60
5,72
Outdoor fans
Fan
Number / type
2 / Axial
2 / Axial
2 / Axial
kW
1,51
1,51
1,51
Sound power
dB(A)
79,8
79,8
86,1
Supply sound power level
dB(A)
84,2
84,2
91,3
Sound pressure at 10 m
dB(A)
48,8
48,8
55,1
Motor power
Sound levels
Dimension and weight
Dimension
Length total / floor
mm
3 740 / 3 295
3 740 / 3 295
3 740 / 3 295
Width / Height
mm
2 285 / 2 150
2 285 / 2 150
2 285 / 2 150
1 685
1 805
1 855
Weight (without option)
kg
1) Following EN 14511 2018. 2) Following EN 14825 2017. 3) Following COMMISSION REGULATION (EU) 2016/2281.
ECOi-RT-Z H · R32 units are available in 3 configurations:
· No damper: unit working with 100% recycled air
· 2 dampers: with outdoor air inlet
· 3 dampers - RECO system: energy recovery system on the exhaust air. This configuration is equipped
with 2 return EC plug fans
R32
HIGH
SEER
HIGH
SCOP
3,82
3,56
ErP
✔
EC MOTOR
GREEN VENTILATION
SCROLL
COMPRESSOR
VERY HIGH
PERFORMANCE
ENERGY
RECOVERY
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.