07 UK HYDRONICS GEN 24 LR - Flipbook - Page 104
R513A
GENERAL INDEX
ECOi-LOOP-N FS H · R513A
Water source heat pumps reversible.
Cooling capacity: 1,7 to 2,0 kW.
Heating capacity: 1,8 to 2,6 kW.
The range at a glance
· 1 version: H (reversible)
· 2 sizes
· Vertical installation
· 4 versions: VC (standard version with cabinet), VCL (low
height version with cabinet), VN (standard version without
cabinet) and VNL (low height version without cabinet)
· EER up to 4,9 and COP up to 4,6
· Nominal air flow from 250 to 460 m³/h
· 3‑speed AC fan (or optional low consumption EC fan)
· Many hydraulic and electric configurations available
· Front or bottom air intake
· Operating range: from 15 °C to 32 °C ambient air
temperature
· Water inlet temperature from 15 °C to 45 °C
Optional controller.
RCS remote control.
Advantages
· Low sound levels: acoustic insulation between ventilation
and compressor compartments
· Design and Elaborate finish cabinet enabling harmonious
integration (RAL9010)
· Low energy consumption EC fan (option)
· Highly customisable. Many air routeing configurations
and selection of hydraulic service side
· Easy access to components through a removable front
panel
· Brazed stainless steel plate heat exchanger for improved
efficiency (coaxial exchanger upon request)
· 100% factory tested
Optional controller.
SRC - mini BMS controller.
SEE PAGE 106 FOR MORE DETAILS ABOUT WATER SOURCE HEAT
PUMPS CONTROL SYSTEMS
Operating limits
Air inlet temperature.
15 °C 1)
23 °C 1)
15 °C
5
10
15
26 °C
20
25
30
35
40
45
50
55
50
55
Water inlet temperature.
23 °C
45 °C
15 °C
5
10
15
32 °C
20
25
30
35
40
45
1) From 21 to 32 °C DB. * Maximum water pressure 10 bars.
AC SELECT.
Smart and user-friendly the new air conditioning
selection program: https://acselect.panasonic.eu/
104
Equipment
· The refrigerant circuit comprises a rotary type hermetic
compressor, a cycle reversal valve, a water/refrigerant
heat exchanger, a liquid receiver, a capillary expansion
device, a finned coil, HP and LP pressure switches and 2
Schrader valves (HP and LP)
· The rotary type hermetic compressor is installed in a
compartment covered with a 20 mm thick Isofeutre
thermal‑acoustic insulation. It is also equipped with
internal thermal protection
· The units are equipped with a control system (POL423)
utilising Modbus RTU
· The water/refrigerant heat exchanger is made of brazed
stainless steel plates, for improved efficiency. A coaxial
heat exchanger is available on request
· RAL9010 painted cabinet for versions VC and VCL
· Condensate drain pan with an anti‑corrosion treatment
· A G2 air filter is provided within the unit