Drivers should be sited somewhere you can access them for maintenance. This
can be up to 60m away from the furthest 昀椀tting.
The driver will often be larger than the hole cut out for the item. Again, locate it in
another place, where you can access it in the future if required
troubleshooting
The first fitting lights up, the others don’t
My fittings are all flashing
guide to constant current LEDs
The driver doesn’t fit through the hole / where do I put the driver?
come on
This is a driver issue. First check your driver
You have wired this in parallel (not in series).
is not overrun or under-run (i.e. within the
You will need to buy replacements for all but
minimum and maximum wattages). Otherwise
the 昀椀rst one.
it is a faulty driver.
These are not repairable.
The first fitting in the circuit stays on after
All the fittings have failed
the circuit is turned off
This is due to driver failure. Check that you
You have residual current in the circuit, or
have wired the circuit correctly, or the driver
current leakage. Try changing the switch. If
may fail again.
these are on a circuit with an intermediate
switch it is almost impossible to prevent a
My fittings come on for a while, then they
small amount of current leakage.
go off, and turn back on by themselves
troubleshooting
later
Your driver is overheating. Improve the air
昀氀ow around it.