Best practices book - Flipbook - Page 132
BEST PRACTICES | 123
CHECK BOX
BELOW IF
REQUIRED
17.
CHECK BOX
BELOW IF
REQUIRED
16.
BEST PRACTICES | 123
2. Fire-Resistant Joint Systems (1705.17.2):
Special Inspection of fire-resistant joint systems that are tested and listed in accordance
with Sections 715.3 and 715.4 shall be conducted by an approved Agency in
accordance with ASTM E 2393.
1. Penetration Firestops (1705.17.1):
Special Inspections of penetration firestop systems that are tested and listed in accordance
with Sections 714.3.1.2 and 714.4.2 shall be conducted by an approved Agency
in accordance with ASTM E 2174.
REQUIRED SPECIAL INSPECTIONS & TESTING
PLEASE PROVIDE THE NAME AND PHONE
NUMBER OF THE SPECIAL INSPECTION
AGENCY AND INDIVIDUAL PERFORMING THIS
SPECIAL INSPECTION SERVICE IN THE SPACE
BELOW.
• In high-rise buildings or in buildings assigned to Risk Category III or IV in accordance with Section 1604.5, Special Inspections for throughpenetrations, membrane penetration firestops, five-resistant joint systems, and perimeter fire barrier systems that are tested and listed
in accordance with Sections 714.3.1.2, 714.4.2, 715.3, and 715.4 shall be in accordance with Section 1705.17.1 or 1705.17.2.
FIRE-RESISTANT PENETRATIONS AND JOINTS (1705.17):
Note: The Registered Design Professional shall indicate on the space to the right and on the
plans the ICC Report approval number for the selected EIFS Application.
Special Inspections are required for all EIFS applications unless one of the following exceptions
applies.
Exception #1: EIFS applications installed over a water-resistive barrier with a means of
draining moisture to the exterior. Please verify the Special Inspection is not
required by the ICC Report of approval for the selected EIFS.
Exception #2: EIFS applications installed over masonry or concrete walls.
REQUIRED SPECIAL INSPECTIONS & TESTING
PLEASE PROVIDE THE NAME AND PHONE
NUMBER OF THE SPECIAL INSPECTION
AGENCY AND INDIVIDUAL PERFORMING THIS
SPECIAL INSPECTION SERVICE IN THE SPACE
BELOW.
EXTERIOR INSULATION AND FINISH SYSTEMS (EIFS) (1705.16 AND 1408.6):