Best practices book - Flipbook - Page 131
BEST PRACTICES | 122
CHECK
BOX
BELOW IF
REQ'D
15.
CHECK
BOX
BELOW IF
REQ'D
14.
BEST PRACTICES | 122
Special Inspections and Tests for mastic and intumescent fire-resistant coatings applied to structural
elements and decks shall be in accordance with AWCI 12-B and shall be based on the fire-resistance
design as designated in the approved construction documents.
REQUIRED SPECIAL INSPECTIONS & TESTING
MASTIC & INTUMESCENT FIRE-RESISTANT COATINGS (1705.15)
Perform Spray Fire-Resistant Materials Inspections per applicable provision of Section 1705.14.
REQUIRED SPECIAL INSPECTIONS & TESTING
PLEASE PROVIDE THE NAME AND PHONE
NUMBER OF THE SPECIAL INSPECTION
AGENCY AND INDIVIDUAL PERFORMING
THIS SPECIAL INSPECTION SERVICE IN THE
SPACE BELOW.
PLEASE PROVIDE THE NAME AND PHONE
NUMBER OF THE SPECIAL INSPECTION
AGENCY AND INDIVIDUAL PERFORMING
THIS SPECIAL INSPECTION SERVICE IN THE
SPACE BELOW.
• Special Inspections and Tests for sprayed fire-resistant materials applied to floor, roof and wall assemblies and structural members
shall be in accordance with Sections 1705.14.1 through 1705.14.6.
• Special Inspections shall be based on the fire-resistance design as designated in the approved construction documents.
• The tests set forth in Section 1705.14 shall be based on samplings from specific floor, roof and wall assemblies and structural members.
• Special Inspections and Testing shall be performed after the rough installation of electrical, automatic sprinkler, mechanical, and plumbing
systems and suspension systems for ceilings, where applicable.
SPRAYED FIRE-RESISTANT MATERIALS (1705.14):