13.4 Seismic Isolation Systems (1705.13.4):
Seismic isolation systems in seismically isolated structures assigned to
Seismic Design Category B, C, D, E or F shall be tested in accordance
with Section 17.8 of ASCE 7-10.
13.3 Designated Seismic Systems (1705.13.3):
For structures assigned to Seismic Design Category C, D, E or F
and with designated seismic systmes that are subject to the
requirements of Section 13.2.2 of ASCE 7-10 for certification, the
Registered Design Professional shall specifiy, on the approved
construction documents, the requirements to be met by analysis
testing or experience data as specified therein.
Certificates of Compliance documenting that the requirements are met
shall be sumbitted to the Building Official as specified in 1704.5.
13.2 Nonstructural Components (1705.13.2):
For structures assigned to Seismic Design Category B, C, D, E
or F, where the requirements of Section 13.2.1 of ASCE 7-10
for nonstructural components, supports on attachments are met
by seismic qualification as specified in Item 2 therein, the
Registered Design Professional shall specifiy on the approved
construction documents the requirements for seismic qualification
by analysis, testing or experience data.
Certificates of Compliance for the seismic qualification shall be
submitted to the Building Official as specified in Section 1705.4.5.
REQUIRED SPECIAL INSPECTIONS & TESTING
TESTING FOR SEISMIC RESISTANCE (1705.13):
CHECK BOX
BELOW IF CONTINUAL
REQUIRED
(2 of 2)
13.
PLEASE PROVIDE THE NAME AND PHONE NUMBER
OF THE SPECIAL INSPECTION AGENCY AND
INDIVIDUAL PERFORMING THIS SPECIAL
INSPECTION SERVICE IN THE SPACE BELOW.