EMERGENCY SHUT-DOWN
SYSTEM (ESD)
Short Response Time
A short response time is essential for valves operating in Emergency Shut Down (ESD) systems
such as in refineries, power stations, mining and other applications where safety regulations
call for such.
The values in the table below indicate the closing time (seconds) of an unloaded actuator and
a loaded actuator with torque values simulating real-life situations. The stroke time measures
the actual movement of the actuator without a solenoid or any other accessory delay.
CompAct actuator stroking time (sec.)
¼" NAMUR solenoid valve
CompAct actuator closing time (sec.)
Normal
CompAct Actuator for
Emergency Shut-Down
(ESD) Systems
Size
¼" Namur solenoid valve
Cv = 0.9
Load
0
C20-2C
C25-2C
C30-2C
C35-2C
C45-2C
C60-2C
C75-2C
3/2
0.09
5/2
0.08
Improved
¼" Namur
solenoid valve
Cv = 0.9, &
Breather Block
3/2
0.05
Fast
¼" Non-Namur
Solenoid valve
Cv = 1, & ¼"
quick exhaust
3/2
0.05
10 Nm / 89 lbf-in
0.14
0.09
0.07
0.07
0
0.17
0.12
0.07
0.06
22 Nm / 195 lbf-in
0.35
0.15
0.17
0.15
0
0.26
0.20
0.12
0.10
36 Nm / 319 lbf-in
0.49
0.23
0.25
0.20
0
0.39
0.29
0.26
0.17
60 Nm / 531 lbf-in
0.58
0.35
0.41
0.27
0
0.71
0.52
0.43
0.30
116 Nm / 1027 lbf-in
1.23
0.64
0.76
0.57
0
1.79
1.30
1.21
0.73
260 Nm / 2300 lbf-in
2.36
1.38
1.73
1.13
0
2.78
2.00
1.86
1.08
460 Nm / 4071 lbf-in
3.90
2.42
2.91
1.75
CompAct actuator closing time (sec.)
Normal
CompAct Actuator for
Emergency Shut-Down
(ESD) Systems
Size
C60-2C
C75-2C
C90M-2C
C100M-SR2C3
Load
0
½" Namur solenoid valve
Cv = 3.5
Fast
½" Non-Namur
Solenoid valve
Cv = 3.5, & ½"
quick exhaust
3/2
0.53
3/2
0.71
5/2
0.49
260 Nm / 2300 lbf-in
1.22
0.60
0.80
0
1.12
-
1.04
460 Nm / 4071 lbf-in
1.79
-
1.52
0
1.4
-
1.2
770 Nm / 6815 lbf-in
2.7
-
2.4
0
2.5
-
2.1
2400 Nm / 21242 lbf-in
4
-
3.4
ACTUATION
467