EN Catalog 2021-22 - Catalog - Page 99
DISCRIMINATING
MAGNETOSTRICTIVE
SENSOR (DMS)
The DMS sensor is a fast acting discriminating sensor that utilizes magnetostrictive
technology to provide reliable monitoring of dispenser pans and containment sumps. Its
floats can detect the presence of water or hydrocarbons and also ensure that the sensor
installation has not been tampered with. The DMS sensor can report water warnings and
programmable water alarm points as well as product alarms.
HIGHLIGHTS
• Utilizes proven magnetostrictive technology.
• Water warning, water alarm, and product alarm.
• Alarms and recovers quickly when hydrocarbons are present.
SPECIFICATIONS
Model
Description
TSP-DMS-12
Discriminating magnetostrictive sensor, monitors 12"
(305 mm) of liquid & measures 22" (559 mm) in length
(all EVO™ Series ATGs)
TSP-DMS-24
Discriminating magnetostrictive sensor, monitors 24"
(610 mm) of liquid & measures 34" (864 mm) in length
(all EVO™ Series ATG).
TSP-KS
Unistrut™ mounting kit
FUEL MANAGEMENT
SYSTEMS
• Tamper protection feature will alarm if sensor is moved
from installed position.
ORDERING INFORMATION
Note: This sensor communicates with the ATG via the TS-PRB probe module.
Applications
For containment sump monitoring.
UNIVERSAL LIQUID
SENSOR (ULS)
Based on float-switch technology and made of chemically-resistant
materials, the ULS is a low-cost sensor that can be installed in sumps,
dispenser pans, steel double wall tanks or other locations where the
presence of liquid indicates a leak has occurred.
HIGHLIGHTS
• Highly reliable float technology and closed output
circuit ensures that leaks are detected.
• Chemical-resistant materials assure compatibility with
most liquids.
• Each ULS sensor comes with a 25' (7.6 m) cable. 1/2" NPT
thread is provided on the compression gland fitting
attached to the sensor’s cable, allowing it to be suspended
from standard electrical boxes and fittings. The sensor may
be positioned vertically by adjusting cable length. For steel
interstitial tanks, ULS is lowered into the opening provided
on the tank and is suspended by optional TSP-KI2
installation kit. Other mounting methods available
depending upon application and location.
SPECIFICATIONS
Applications
For containment sump monitoring.
ORDERING INFORMATION
Model
Description
FMP-ULS
Universal liquid sump sensor (all EVO™ Series ATGs)
TSP-ULS
Universal liquid sump sensor (for use with S940 only)
TSP-KI2
Interstitial sensor riser cap kit for 2" (51 mm) riser pipes
Note: This sensor communicates to the ATG using 2 wires on the 2-wire sensor
modules or the 3-wire sensor module. It cannot be wired to the probe module.
99