EN Catalog 2021-22 - Catalog - Page 91
TS-LS500
AUTOLEARN™ ELECTRONIC
LINE LEAK DETECTION
TS-LS500 AutoLearn™ electronic line leak detection (ELLD) learns the
characteristics of each line, eliminating possible configuration errors and
ensures unparalleled leak detection accuracy. It is an optional feature of
the EVO™ 550, EVO™ 5000, EVO™ 600, and EVO™ 6000 fuel management
systems. The TS-LS500 AutoLearn™ ELLD system includes a statistical
line leak detection (SLLD) feature which can be activated at high
throughput sites that cannot accommodate the prolonged downtime
necessary for static line leak detection testing.
SPECIFICATIONS
• Automatically learns exact pipeline characteristics.
• Dimensions: 6¼" × 2" NPT
• No pipe type and length programming required.
• Operating temperature: -40 °F to 149 °F (-40 °C to 66 °C)
• Monitors flexible, steel, and/or fiberglass pipelines in any
combination up to certified maximum values.
• Operating pressure: 0 to 100 psi (0 to 689 kPa)
• Works with submersible pumps generating 25 psi or more.
• Belden™ cable: #9363-22 AWG, #9364-20 AWG or
#9365-18 AWG
• Automatically performs 3.0 gph, 0.2 gph, and 0.1 gph line
tests, as well as other line pressure checks.
• Maximum sensor to ATG cable distance: 500' (152.4 m)
• Includes the industry’s only statistical line leak
detection (SLLD).
• Sensor material: Anodized aluminum body and stainless
steel sensor
• Positive submersible pump shutdown in the event of a leak.
• Optional feature of the EVO™ 550, EVO™ 5000, EVO™ 600,
EVO™ 6000.
• Intrinsically safe and explosion-proof options.
• Dispenser hook isolation and turbine pump interface (TPI)
pump control options.
• Remote access to line pressure, test, and alarm information.
FUEL MANAGEMENT
SYSTEMS
HIGHLIGHTS
• Sensor port fitting: 2" female NPT
Capabilities
• Performs a 3.0 gph leak and pressure test after every
dispense cycle or 45 min. Positive shutdown of the affected
turbine(s) on test failure.
• Performs a 0.2 gph monthly and 0.1 gph annual precision
leak test during the thermally stable periods of dispensing.
Optional positive shutdown of the affected turbine(s) on
test failure.
• Performs pressure up, catch pressure, and other additional
checks. Alarm only on test failure.
Approvals
• TS-LSU500: UL, cUL, ATEX, IECEx
• TS-LSU500E: UL, cUL
• Third party certification of leak detection capabilities.
91