EN Catalog 2021-22 - Catalog - Page 37
PRESSURE/VACUUM RATING
The values listed below have been qualified by third party approvals testing.
Rated Pressure
Rated Vacuum
Typical Burst Pressure
UPP ® Extra &
EN14125:2013 Pipes
Bar
Psi
Bar
"Hg
Bar
Psi
Primary Pipe
10
145
-0.9
-26.6
40
580
Secondary Pipe
5
58
-0.6
-17.7
20
290
Fill Pipe
6
87
n/a
n/a
30
435
Electrical Conduit
10
145
-0.9
-26.6
40
580
Corrugated Duct
n/a
Primary Pipe
6.2
90
-0.9
-26.6
40
580
Un-Lined Vent Pipe
4
58
-0.6
-17.7
20
290
PIPING &
CONTAINMENT
UL971 Pipes
BEND RADIUS
Q: Because UPP® is semi-rigid, what bend radius is possible during installation?
A: This is largely temperature dependent, but in general you may use these values for single or double wall UPP® delivered as coils:
50 mm
63 mm
90 mm
110 mm
Warm Weather
15 x Ø
80 cm
1m
1.5 m
3m
Cold Weather
25 x Ø
140 cm
1.6 m
2.5 m
4m
Very Cold Weather
35 x Ø
190 cm
2.2 m
3.5 m
5m
For UPP® in 5.8 m straight lengths welded together and then curved to suit the required layout you can expect:
50 mm
63 mm
90 mm
110 mm
Warm Weather
30 x Ø
1.5 m
2m
3m
4m
Cold Weather
60 x Ø
3m
3m
5m
6m
Very Cold Weather
80 x Ø
4m
4m
7m
8m
INTERSTITIAL VOLUME
When using leak detection equipment it is often necessary to know the interstitial volume of double wall pipes to decide the
amount of compressed gas or type of pumped detection unit required. Below are the volumes per metre of UPP® pipework.
Double Wall Pipe
40/32 mm
63/50 mm
75/63 mm
110/90 mm
125/110 mm
160/90 mm
160/110 mm
(1 ")
(1½")
(2")
(3")
(4")
(3")
(4")
Litres / m
0.24
0.66
0.62
2.15
0.97
10.79
7.64
Cubic Inches / ft
4.40
12.29
11.52
39.93
18.01
200.73
142.12
63/50 mm
75/63 mm
110/90 mm
125/110 mm
Interstitial Volume
UL971 Double Wall Pipe
Interstitial Volume
(1½")
(2")
(3")
(4")
Litres / m
0.12
0.13
1.41
0.45
Cubic Inches / ft
2.25
2.43
26.21
8.35
37