SPECIFICATIONS CONTINUED
Number of
Dispenser Channels
4 to 16 Dispensers
E-Stop Control Input
120VAC Hard-Wired Connection
Number of Conductors
Disconnected per Dispenser
(Dependent on Model)
Dispenser Data: 4 Conductors
Signal Circuit Rating
Class 2, 48V Max, 3 Amp
Surge Protection Available
Optional for Dispenser Data Circuits
Individual Channel
Control Switches
Yes
Dispenser Power Sensing
Yes
Lockable Channel
Control Switches
Yes
Secondary Remote
Expansion Output
Yes
Ethernet: RJ45
Dispenser Data & Credit Card Circuits
2 Wire Current Loops
- Standoff Voltage
47.8V
- Breakdown Voltage
56V Max +/- 5%
- Clamp Voltage
77V Max
- Peak Pulse Current
19.7A
UL Listed 508A
- For compliance with NEC®
514.11 and NFPA® 30A Section
6.7 requirements for Emergency
Disconnects at Motor Fuel
Dispensing Facilities (controlled
by E-Stop system)
Intercom Circuits: 4 or 8 Conductors
Surge Protection Specifications (Generic “P” Option)
388
Approvals
Certifications
- For compliance with NEC®
514.13 requirements for
Maintenance Disconnects at
Motor Fuel Dispensing Facilities
(switches to disconnect
individual dispenser circuits
for servicing)