ORDERING INFORMATION
Site Requirements
• EVOTM 550/5000 or EVOTM 600/6000 fuel management systems
• TS-ELLD software options (TS-ELLD-G software option for generator-specific applications)
• TS-ACI, TS-420IB or TS-420EXP, *TS-RLY Modules
* TS-RLY Module is not required when utilizing Turbine Pump Interface (TPI) communications. Franklin Electric intelligent pump controllers required.
Minimum Pressure Requirements
Item
Value
15 PSI (103.4 kPa) for gross 3 GPH test
18 PSI (124.1 kPa) monthly .2 Precision test
Minimum Static Pressure
18 PSI (124.1 kPa) annual .1 Precision tests
20 PSI (137.9 kPa) for learning lines
Pipe Length to Hold Minimum Line Volume
Pipe diameter ID
1"
1 ½"
1 ¾"
2"
2 ½"
3"
4"
5"
Both Flex & Rigid Length
61'
27'
20'
15'
10'
7'
4'
2'
Metric
(18.6 m)
(8.2 m)
(6.0 m)
(4.6 m)
(3.0 m)
(2.1 m)
(1.2 m)
(0.6 m)
Pipe Length to Hold Maximum Line Volume
Pipe diameter ID
1"
1 ½"
1 ¾"
2"
2 ½"
3"
4"
5"
Flex Length
2339'
(713 m)
1040'
(317 m)
764'
(233 m)
585'
(178 m)
374'
(114 m)
260'
(79 m)
146'
(45 m)
94'
(29 m)
Rigid Length
7656'
(2334 m)
3403'
(1037 m)
2500'
(762 m)
1914'
(583 m)
1225'
(373 m)
851'
(259 m)
479'
(146 m)
306'
(93 m)
Maximum and Minimum Line Volume for Rigid and Flexible Pipe
Item
Volume
Maximum line volume for rigid pipe
312.2 gal (1181.8 L)
Maximum line volume for flexible pipe
95.4 gal (361.1 L)
Minumum line volume for rigid or flexible pipe
2.5 gal (9.5 L)
Intrinsically Safe
For new installations where separate low voltage conduits can be used. Use TS-420IB Module.
Model
Description
LS500/2
2-line transducer kit
LS500/3
3-line transducer kit
LS500/4
4-line transducer kit
Explosion-Proof
For retrofit installations where only a high voltage conduit can be used. Use TS-420EXP Module.
Model
Description
LS500E/2
2-line transducer kit, explosion-proof
LS500E/3
3-line transducer kit, explosion-proof
LS500E/4
4-line transducer kit, explosion-proof
Alternative Fuels Accessories
326
Model
Description
TS-AFALNIP