UL Catalog 2024-2025 - Flipbook - Page 320
ORDERING INFORMATION
Ordering Guide
EVO™ model, software and hardware options can be listed separately or combined when ordering. Systems shipped from the factory
will list the combined part number. Complete part numbers have a specific order and are created using the following guidelines:
TRFLGSC = Software Options (choose all that apply)
EVOX DPWIE / TRFLGC
T = SCALD® 24-hour tank testing
EVOX = Base Model Options
R or F = (R) Reconciliation/Autocalibration or
EVO600 = EVO™ 600 base model
(F) Reconciliation/Autocalibration with
Flow Rate Monitoring
EVO6000 = EVO™ 6000 base model
DPWIE = Hardware Options (choose all that apply)
L or G = (L) Electronic Line Leak Detection or
D = Display
(G) Generator Electronic Line Leak Detection
P = Printer
S = Secondary Containment Monitoring
W = WiFi
C = Enhanced logic conditions including value, counter,
value compare, latch, and DEF/AdBlue® recirculation.
I = Dispenser Interface Module
Example: EVO600DPWI/TRL = EVO™ 600 base model with display, printer, WiFi, Dispenser Interface Module, SCALD®, Reconciliation/Autocalibration, and line leak detection.
Dispenser Interface Module Cables
Model
Description
TSP-BDCBL
Bennett® 515 only cable
TSP-GDCBL
Gilbarco® cable
TSP-GSDCBL
Gilbarco® G-Site™ cable
TSP-WDCBL
Wayne™ cable
EVO™ 600/6000 Interface Modules
The EVO™ 600/6000 come standard with a Power Supply Module and a controller module. Additional interface modules can be
installed. Interface modules ordered with an EVO™ will be installed at the factory. If you would like them to not be installed, please
order the spare/replacement version of the module. The following guidelines must be followed:
•
EVO™ 600: Six total modules can be installed with a maximum of four intrinsically safe modules and a maximum of three of any
one kind of module, except for the UDP Module, which allows for a maximum of four modules.
•
EVO™ 6000: Eleven total modules can be installed with a maximum of nine intrinsically safe modules and a maximum of three of
any one kind of module, except for the UDP Module, which allows for a maximum of six modules.
Note: Do not include the Power Supply and Controller Modules when calculating total modules allowed.
Maximum UDP Modules Allowed to Run Concurrently with Probe Modules in a Single EVO™ Console or Expansion Console
The UDP Module is intended to replace the Probe Module for all new system orders. If you are planning to add UDP Modules to an
existing EVO™ 600/6000 with Probe Modules, please adhere to the following table:
320
Existing Probe Modules
Allowable UDP Modules
0
6
1
4
2
2
3
0