EVO™ 600 &
EVO™ 6000 SERIES
EVO™ 600 & EVO™ 6000 provide highly accurate inventory management and
full-featured compliance monitoring for any size fuel system. Being module-based,
the EVO™ Series is highly configurable for site-specific probe and sensor
requirements. Their simple setup and operation, remote connectivity, and advanced
security features protect your fuel system while keeping you directly connected to
vital site data whenever, and wherever. The highly-intuitive, full-color, icon-based
touch screen provides user-friendly on-site access to inventory, alarm, and
compliance data.
HIGHLIGHTS
• Allows you to make informed, data-driven inventory management
decisions while keeping your site in compliance and protected
from security threats.
•
Included Features: Inventory monitoring, Turbine Pump Interface
Maximum AC input channels, with accessories
72* (EVO™ 600) / 72* (EVO™ 6000)
Maximum AC input channels, with accessories
72* (EVO™ 600) / 72* (EVO™ 6000)
Maximum relay output channels (stand-alone)
26 (EVO™ 600) / 26 (EVO™ 6000)
Maximum relay output channels, with accessories
50* (EVO™ 600) / 50* (EVO™ 6000)
Dry contact input channels
2
(TPI) capability for enhanced and automated submersible turbine
pump control, static tank testing, and containment compliance
monitoring.
•
Optional Features: 24-hour Statistical Continuous Automatic Leak
Detection (SCALD®), tank autocalibration, inventory reconciliation,
Ethernet (qty 2). RS-232, RS-485, standard USB,
Connectivity
Mini-B USB
Display type
7" (17.78 cm) color LCD touch screen
• Patented AutoLearn™ electronic line leak detection capability
including Statistical Line Leak Detection for high throughput sites.
Printer type
Thermal (also network or USB)
• Streamlined setup and programming includes hardware
auto-detection and wiring confirmation, multipoint tank charting,
network printer auto-detection, and the ability to download and
upload entire programming profiles from one EVO™ to another.
Alarm
Internal audible alarm
LEDs
Alarm, warning, and power
Applicable liquids
Petroleum, chemicals, and waste
Level units
Inches, centimeters, and millimeters
secondary containment monitoring, and flow rate monitoring.
•
Intuitive full-color 7" (17.78 cm) LCD touch screen interface
provides simplified on-site access features including:
•
Up to Six (6) One Touch Buttons that are custom programmed
to carry out common automated tasks with a single tap.
•
A Quick Jump Menu that allows you to quickly maneuver from
Gallons or liters (mass with
Volume units
density option)
Power requirements
110 to 240 VAC, 50/60 Hz, 1.5 Amps
Operating temperature
32° to 104° F (0° to 40° C)
Humidity
0-90% non-condensing
EVO™ 600
H: 11.75"(300 mm), W: 10¼"(260 mm), D: 9"(229 mm)
EVO™ 6000
H: 11.75"(300 mm), W: 16½"(419 mm), D: 9"(229 mm)
Alarm set points
High/low product, water, and temperature
application to application using a single button.
•
•
Programmable product colors for each tank.
FFS PRO® Connect allows you to remotely connect to your EVO™
from any web-enabled device.
•
Optional WiFi allows secure and protected on-site viewing of
inventory levels for fuel delivery drivers.
• Compatible with the Multiplexing Sensor Hub™ (FMP-MSH).
• Compatible with Corrosion Control™ Water Separator.
• Supports MQTT protocol, the standard for IoT messaging, for
enhanced security of data transmission.
Maximum tanks monitored
(stand-alone)
Maximum tanks monitored,
with accessories
Maximum sensor input
capacity (stand-alone)
Maximum sensor input
capacity, with accessories
Maximum total inputs
(stand-alone)
Technical Advantages
Inventory reconciliation/tank autocalibration/
flow rate monitoring
Measurements
Density, mass, and phase separation measurement
Notifications
Email and SMS
Programming
Back-up generator monitoring/conditions
Advanced Logic Control
DEF/AdBlue® recirculation system
48 (EVO™ 600) / 108 (EVO™ 6000)
Support
MQTT, MODBUS™, XML, Veeder-Root®
180* (EVO™ 600) / 244* (EVO™ 6000)
Approvals / Certifications
–
–
–
48 (EVO™ 600) / 72 (EVO™ 6000)
132* (EVO™ 600) / 168* (EVO™ 6000)
UL, cUL, ATEX, IECEx, GSA IT Security
Third party certification of leak detection capabilities
Third party verified “MATURE” security posture level
72 (EVO™ 600) / 132 (EVO™ 6000)
*Requires use of FMP-EXPC Expansion Modules and/or FMP-MSH Multiplexing Sensor Hubs.