FLEX-ING® FLEXIBLE CONNECTOR: I N S T A L L A T I O N
EVO™ SERIES CABLE: S P E C I F I C A T I O N S
PROVIDE SUPPORT
Franklin Electric requires the use of cable with specifications listed below when
installing EVO™ Series components. It is required to follow the specifications below.
Please consult the cable manufacturer for specifications.
BELDEN CABLE TO USE WITH EVO™ SERIES EQUIPMENT
When installing the assembly in a
horizontal loop, provide support for the
arms to prevent the hose from sagging.
WRONG
No support, sagging
and sharp bends
CORRECT
E V O ™ S E R I E S C O M P O N E N T S T H AT U S E S H I E L D E D T W I S T E D P A I R C A B L E
Support
Probes (TSP-LL2 and FMP-LL3)
Line Leak Transducers (TS-LSU500)
Motion
DO NOT TORQUE
D U R I N G I N S TA L L AT I O N
Metal hose assemblies should not
be used to compensate for bolt hole
misalignment. Floating flanges will help
to minimize twisting of the metal hose.
Pipe unions help to reduce twisting
during connection to the piping, Use
two wrenches to help keep the hose
from twisting when tightening the
pipe union.
Discriminating Magnetostrictive Sensor (TS-DMS)
C O M M O N C A B L E S P E C I F I C AT I O N S
Motion
Shielded Twisted Pair
Wire must be 22AWG or greater
Cable jacket must be oil/water resistant
FOR CABLE RUNS UP TO 500 FEET
CORRECT
In-plane flexing
WRONG
Out-of-plane flexing
Capacitance is rated less than 100 picofarad (pF) per foot
Inductance is rated less than 0.2 µH/ft.
Belden cable that meet these requirements:
M A I N TA I N M I N I M U M
CENTER-LINE BEND RADIUS
• 87760, 87761
WRONG
The hose assemblies must not be forced
to a bend radius less than specified.
HOSE SIZE
0.25", 1", 1.5", 2"
3"
4"
MIN. BEND RADIUS
6" (152 mm)
9" (228 mm)
13" (330 mm)
If you have questions about installing Franklin Electric
flexible connectors, contact FFS Technical Support at
800-984-6266.
FOR CABLE RUNS UP TO 1,000 FEET
Capacitance is rated less than 60 pF per foot
Inductance is rated less than 0.2 µH/ft.
CORRECT
R
Belden cable that meet these requirements:
• 88760, 8760, 8770
FOR CABLE RUNS UP TO 1,500 FEET
Capacitance Conductor to Conductor is rated less than 20 pF per foot
MINIMUM BEND RADIUS FROM CENTER-LINE OF HOSE
Inductance is rated less than 0.3 µH/ft.
Belden cable that meet these requirements:
• 89182