FFS-0772 Forecourt Guide No 6 InteractiveSpreads - Flipbook - Page 19
UPP® PIPE: I N S E R T I O N
DEPTH
MA R K IN G IN S ERTION DEPTH BY PR E- F ITTIN G :
M A R K I NSE R T IO N D EP T H :
Mark the insertion depth on pipe ends using a permanent marker or China-graph
pencil and a ruler.
The insertion depth can also be marked by inserting the cleaned pipe fully into the
fitting and marking around the fitting.
Using a ruler to mark insertion depth.
UPP EXTRA PIPEWORK SYSTEM
Inscribe a line around the junction of the pipe and fitting.
The following table shows the correct insertion depth into UPP® primary electrofusion fittings.
Note: When using this method, make sure the pipe is fully inserted. Visually check if possible, or listen/feel for the pipe
positively contacting the stop.
INSERTION LENGTH
DESCRIPTION
Welding Coupler
90° Elbow Electrofusion
45° Elbow Electrofusion
Flexible Entry Boot
MM
PRODUCT CODE
MM
INCHES
50
02-50
25
1
63
02-63
30
13/16
90
02-90
36
13/8
110
02-110
41
19/16
50
03-050-EIF
44
13/4
63
03-063-EIF
48
17/8
90
03-090-EIF
62
27/16
110
03-110-EIF
71
23/4
63
04-063-EIF
47
17/8
90
04-090-EIF
62
27/16
110
04-110-EIF
72
23/4
75
FEB-075-M
92 - 94
35/8
110
FEB-110-M
127 - 129
5
125
FEB-125-MM
144 - 153
53/4 or 6
NOTES:
37