FFS-0772 Forecourt Guide No 6 InteractiveSpreads - Flipbook - Page 11
GUARDIAN SPGC-220 SMART CONTROLLER: D I P
SWITCH OPTIONS
DESCRIPTION
FUNCTION
1
Fault Shutdown
When this is ON, an abnormal condition detected
on any controller in a Primary-Secondary or AC
configuration causes all connected controllers to
shut down.
2
Unused
The default position is ON.
3
PrimarySecondary
ON designates the SPGC-220 as the Primary
controller. This switch must be set to OFF for
Secondary and Stand Alone configurations.
4
AC
When the Primary controller is ON, the AC feature
is active. OFF indicates a Secondary or Stand Alone
configuration.
5
Extended Run
Disable
ON disables the extended run feature.
OFF activates the extended run feature.
6
DEF Mode
ON enables use with Diesel Exhaust Fluid submersible
(for models DEF-PMA150A or DEF-PMA150B only)*
7
Unused
ADDRESS
SW2
Unused
DESCRIPTION
1
Address 0
2
Address 1
3
Address 2
4
Address 3
5
FUNCTION
Use poles 1-5 to set the addressing switches for
Primary-Secondary or AC configurations.
Address 4
6
Fault Readout
ON activates the fault readout function.
7
Bypass
ON bypasses diagnostics for 10 minutes.
8
Auto Restart
When ON, the controller tries to restart the STP in an
underload (UL) fault condition.
*DEF Mode is available only with SPGC-220 revision 0.3.8 firmware or higher.
(The firmware revision is shown when the controller starts up and resets.)
O 1 2 3 4 5 6 7 8
N
SW1:
POLE
1
2
3
4
5
OFF
OFF
OFF
OFF
OFF
Secondary - 1
ON
OFF
OFF
OFF
OFF
Secondary - 2
OFF
ON
OFF
OFF
OFF
Primary
Unused switch. The default position is OFF.
8
SETTINGS
POLE
O 1 2 3 4 5 6 7 8
N
POLE
GUARDIAN SPGC-220 SMART CONTROLLER: A D D R E S S I N G
SW1:
SW2:
SW1
Secondary - 3
ON
ON
OFF
OFF
OFF
Secondary - 4
OFF
OFF
ON
OFF
OFF
Secondary - 5
ON
OFF
ON
OFF
OFF
Secondary - 6
OFF
ON
ON
OFF
OFF
Secondary - 7
ON
ON
ON
OFF
OFF
Secondary - 8
OFF
OFF
OFF
ON
OFF
Secondary - 9
ON
OFF
OFF
ON
OFF
Secondary - 10
OFF
ON
OFF
ON
OFF
Secondary - 11
ON
ON
OFF
ON
OFF
Secondary - 12
OFF
OFF
ON
ON
OFF
Secondary - 13
ON
OFF
ON
ON
OFF
Secondary - 14
OFF
ON
ON
ON
OFF
OFF
Secondary - 15
ON
ON
ON
ON
Secondary - 16
OFF
OFF
OFF
OFF
ON
Secondary - 17
ON
OFF
OFF
OFF
ON
Secondary - 18
OFF
ON
OFF
OFF
ON
Secondary - 19
ON
ON
OFF
OFF
ON
Secondary - 20
OFF
OFF
ON
OFF
ON
Secondary - 21
ON
OFF
ON
OFF
ON
Secondary - 22
OFF
ON
ON
OFF
ON
Secondary - 23
ON
ON
ON
OFF
ON
Secondary - 24
OFF
OFF
OFF
ON
ON
Secondary - 25
ON
OFF
OFF
ON
ON
Secondary - 26
OFF
ON
OFF
ON
ON
Secondary - 27
ON
ON
OFF
ON
ON
Secondary - 28
OFF
OFF
ON
ON
ON
Secondary - 29
ON
OFF
ON
ON
ON
Secondary - 30
OFF
ON
ON
ON
ON
Secondary - 31
ON
ON
ON
ON
ON
NOTE: The default factory
setting is the Stand Alone
configuration with all
selectable features off:
Fault Read out, Bypass,
Auto Restart, Fault
Shutdown, and Extended
Run Disable.
If your SPGC-220
includes the SW3 option
select switch, leave all
poles in the OFF position.
(This is the factory
default.)
The Rotary Select Switch
adjacent to SW3 is to be
left at position 0 (factory
default), unless you are
instructed by Technical
Support to change it. If
the Rotary Select Switch
is moved from position 0,
there could be calibration
and operation issues with
your SPGC-220.
21