FFS-0772 Forecourt Guide No 6 InteractiveSpreads - Flipbook - Page 10
Sets addressing for Primary Secondary / Turbine Pump Interface configurations.
7
Not used
6
Not used
5
Proportional alternating (see manual)
4
Timed alternating (see manual)
3
IST-VFC
ON: Communication with IST-VFC active
OFF: Communication with MagVFC™ or EcoVFC™ active
2
FAULT SHUTDOWN
ON: All pumps disabled if one is in alarm
OFF: Only the pump in alarm is disabled
1
EXTEND RUN
ON: Extended run disabled | OFF: Extended run active
8
ALTERNATING CIRCUIT
ON: Primary controller only | OFF: No alternating or Secondary
7
AUTOMATIC RESTART
ON: Controller will reset UL alarm when hook applied
OFF: Manual reset of UL alarm required
6
PMA HORSE POWER
ON: VS4 | OFF: VS2
5
Pipe compensation (see manual)
4
Pipe compensation (see manual)
3
ON: Primary Secondary or Primary Secondary alternating
OFF: Stand-alone Secondary
2
ON: Gasoline products | OFF: Diesel products
1
MLD VS. PLLD
ON: 6 second PSI increase to 34 PS
OFF: 8 PSI increase for 6 seconds
1
2
3
4
5
5
OFF
OFF
OFF
OFF
OFF
OFF
4
OFF
OFF
OFF
OFF
OFF
OFF
3
OFF
OFF
OFF
OFF
ON
ON
2
OFF
OFF
ON
ON
OFF
OFF
1
OFF
ON
OFF
ON
OFF
ON
SW2
SW1 OPTIONS:
Sets the submersible turbine pump output psi.
SW6
SW1 SWITCH POSITION
DESCRIPTION
0
24 psi
1
26 psi
2
28 psi
3
30 psi
4*
32 psi
5
34 psi
6
36 psi
7
38 psi
8
40 psi
9
42 psi
7 8
0 1
DESCRIPTION
PRIMARY
9
SW3
SECONDARY
SW2 POLE
5 6
Not used
4
DESCRIPTION
8
O 1 2 3 4 5 6 7 8
N
SW6
O 1 2 3 4 5 6 7 8
N
SW2 OPTIONS:
Sets site and motor requirements.
O 1 2 3 4 5
N
S WITCH SETT I NG S
SW6 & SW3 OPTIONS:
2 3
MAGVFC™/ ECOVFC™ VARIABLE SPEED CONTROLLER: DIP
SW1
SW3
SW3
* Factory setting
19