662 SERIES PRODUCT
SHEAR VALVE
EBW® brand emergency shear valves immediately stop
product flow in the event of fire or collision at the dispenser.
A patented adapter shears clean upon impact, causing the
poppet to seal on the valve body preventing fuel spillage.
When fire occurs, a fusible link releases the fulcrum arm,
engaging the poppet. Standard 1½" NPT openings allow
minimal flow restriction and a pre-drilled test plug is included
for line pressure testing. The valve can be boss or U-bolt
mounted. Easy-to-replace adapters slide on and off valve
base without lifting the dispenser. Adapters are available in
male, female or union connections. Single poppet models
stop product flow from the pump. Double poppet models
stop flow from the pump and dispenser piping.
HIGHLIGHTS
SPECIFICATIONS
•
Fusible link closes poppet in the event of a fire
(165.0 °F and 73.9 °C).
•
•
Single and double poppet.
•
•
•
•
•
•
•
•
E-coated body corrosion protection.
Main poppet seals in valve body, preventing accidents
when replacing adapters.
Meets NFPA 30A requirements.
AGB compatible (E-85, gasoline and Biodiesel).
UL 842A and UL 842B approved for E-85 alcohol/gas
blends and biodiesel.
ORDERING INFORMATION
Model
Description
662500901
Single poppet, union, 1½" NPT, E-coat AGB
662500902
Single poppet, female, 1½" NPT, E-coat AGB
662500903
Single poppet, male, 1½" NPT, E-coat AGB
662510902
Single poppet, female, 1½" BSPT, E-coat AGB
662510903
Single poppet, male, 1½" BSPT, E-coat AGB
662501901
Double poppet, union, 1½" NPT, E-coat AGB
662501902
Double poppet, female, 1½" NPT, E-coat AGB
662501903
Double poppet, male, 1½" NPT, E-coat AGB
662511902
Double poppet, female, 1½" BSPT, E-coat AGB
662511903
Double poppet, male, 1½" BSPT, E-coat AGB
662502902
Double poppet, normally closed, female, 1½" NPT,
E-coat AGB
662502902 is UL listed only.
124
Top and body material: E-coat cast iron
Poppet and O-ring: Fluorocarbon
Stem and poppet spring: Stainless steel
The closing feature of an automatic shut-off valve must be
checked at least once per year by manually tripping and
holding linkage.
Approvals
• UL and ULC listed
•
•
UL 842 A&B approved for ethanol and biodiesel
ATEX approved, SIRA 13ATEX9035U
Note: The closing feature of an automatic shut-off valve must be checked at least
once per year by manually tripping and holding linkage.
NFPA-WARNING
Annually test auto shut-off. Electrical supply to the
submersible pump must always be disconnected before
servicing meters, dispensers, or emergency shut-off valves.
Do not apply more than 50 psi to valve with poppet in its
closed position. Valve seat and disc damage may occur.