3.21 S E R V I C E D U C T
USE OF SPACE
CAPACITY
The Area to House Services Connecting to Toilets
Not Applicable
DESCRIPTION OF SPACE
A space dedicated for locating services connecting to toilets, including flushing systems and
the like.
To provide a fully enclosed area for these and other similar services.
This space is a separate room and not an enclosed space within the toilet areas that is accessed
though a wall panel.
A door to this space from a Female Toilet, Male Toilet or Universal Access Toilet is not suitable.
Ensure there is a minimum 600mm wide clear area in the duct to manoeuvre in the space to service
the equipment, fixtures and fittings located there.
CONNECTED SPACES
Directly Connected to:
Outside
Indirectly Connected to:
Female Toilet | Male Toilet | Universal Access Toilet
DIMENSIONS OF SPACE
Nominal Area
Nominal Length
Nominal Width
Min Ceiling | Soffit Height
6 m2
6,000 mm
1,000 mm
2,600 mm
REFERENCE DOCUMENTS THAT APPLY
Camden Council
Consultation with Camden Council to establish specific requirements.
MATERIALS
LOCATION
Floor
Skirting
Wall
Material
Finish
Concrete Slab
Trowel
None Required
9 mm Fibre
r
None
Cement Sheet
CAMDEN PUBLIC BUILDING DESIGN MANUAL
Colour
Dimension
NOTE
White Colours are
r
r
r
r
not suitable