3.20 O P E R A T I O N A L S E R V I C E S
USE OF SPACE
CAPACITY
The Area for Operational Equipment Servicing the Building
Not Applicable
DESCRIPTION OF SPACE
A space dedicated for locating operational services such as distribution boards and the like.
To provide a fully enclosed area for irrigation controls and other services.
No other item is permitted to be located within this space.
CONNECTED SPACES
Directly Connected to:
To Suit Building
Indirectly Connected to:
DIMENSIONS OF SPACE
Nominal Area
Nominal Length
Nominal Width
Min Ceiling | Soffit Height
6 m2
1,000 mm
6,000 mm
2,600 mm
REFERENCE DOCUMENTS THAT APPLY
Camden Council
Consultation with Camden Council to establish specific requirements.
MATERIALS
LOCATION
Floor
Skirting
Wall
Material
Finish
Concrete Slab
Trowel
NOTE
White Colours are
r
r
r
Paint
r
Brickwork
Face
r
9 mm Fibre
Paint
r
None Required
9 mm Fibre
Cement Sheet
PAGE 146
Dimension
r
Cement Sheet
Ceiling
Colour
not suitable
APPENDIX A - COMMUNIT Y CENTRE